Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
NOT
ID
MET
N/A
REMARKS
PREFIX
(PROMPT OR SLOW EVACUATION)
MET
PROTECTION
K300
Protection – Other
List in the REMARKS section any LSC Section 33.2.3 Protection
requirements that are not addressed by the provided K-tags, but are deficient.
This information, along with the applicable Life Safety Code or NFPA standard
citation, should be included on Form CMS-2567.
K311
Vertical Openings – Enclosure
Vertical openings shall be enclosed or protected in accordance with 8.6
unless:
1. Unprotected vertical openings not part of required egress shall be
permitted by the authority having jurisdiction where such openings do not
endanger required means of egress. This shall apply only in buildings
protected throughout by an approved automatic sprinkler system in
accordance with 33.3.3.5, and exits and required ways of travel thereto
are adequately safeguarded against fire and smoke within the building, or
in which every individual room has direct access to an exterior exit without
passing through a public corridor.
2. In buildings not more than two stories in height, unprotected vertical
openings shall be permitted by the authority having jurisdiction if the
building is protected throughout by an approved automatic sprinkler
system in accordance with 33.3.3.5.
No floor below the level of exit discharge used only for storage, heating
equipment, or purposes other than residential occupancy shall have
unprotected openings to floors used for residential occupancy.
33.3.3.1.1.1, 33.3.3.1.1.2, 33.3.3.1.1.3, 33.3.3.1.3
K321
Hazardous Areas – Enclosure
Rooms containing high-pressure boilers, refrigerating machinery,
transformers, or other service equipment subject to possible explosion shall
not be located under or adjacent to exits. All such rooms shall be effectively
separated from other parts of the building as specified in section 8.7.
Hazardous areas shall be separated with construction of a minimum of 1-hour
fire resistance with openings protected with self-closing fire doors or have an
automatic extinguishment system and smoke partition in accordance with 8.4.
Hazardous areas shall include but not be limited to the following: boiler or
heating rooms, laundries, repair shop, spaces storing combustibles in
quantities deemed hazardous.
33.3.3.2.1, 33.3.3.2.2