Name of Facility
2012 LIFE SAFETY CODE
ID
MET
NOT
N/A
REMARKS
PART III – NEW RESIDENT BOARD & CARE OCCUPANCIES
PREFIX
MET
K332
Interior Floor Finish
Interior floor finish shall comply with 10.2.
Interior floor finish in exit enclosures and exit access corridors and spaces not
separated from them by walls complying with 32.2.3.6 shall not be less than
Class II.
Interior floor finish shall comply with 10.2.7.1 or 10.2.7.2, as applicable.
32.3.3.3.3.1, 32.3.3.3.3.2, 32.3.3.3.3.3
K341
Fire Alarm System – Installation
A fire alarm system shall be installed, maintained, and tested in accordance
with section 9.6.
32.3.3.4.1
K342
Fire Alarm System – Initiation
The required fire alarm system shall be initiated by each of the following
means:
1. Manual means in accordance with 9.6.2.
2. Manual fire alarm box located at a convenient central control point under
continuance supervision of responsible employees.
3. Required automatic sprinkler system.
4. Required detection system.
32.3.3.4.2
K343
Fire Alarm – Notification
Occupant notification shall be provided automatically, without delay, by
internal audible alarm in accordance with 9.6.3.
High-rise buildings shall be provided with an approved emergency
voice/alarm system in accordance with 11.8.
Emergency forces notification shall meet the following requirements:
1. Fire department notification in accordance with 9.6.4.
2. Smoke detection devices shall initiate a positive alarm sequence in
accordance with 9.6.3.4 for not more than 120 seconds.
An annunciator panel, connected to the fire alarm system, shall be provided
at a location readily accessible from the primary point of entry for emergency
response personnel.
32.3.3.4.3, 32.3.3.4.4, 32.3.3.4.5, 32.3.3.4.6
Form CMS-2786W (10/2016)