Form Cms-2786w - Fire Safety Survey Report - Icf-Iid (Large Facilities) 2012 Life Safety Code Page 20

ADVERTISEMENT

Name of Facility
2012 LIFE SAFETY CODE
ID
MET
NOT
N/A
REMARKS
PART III – NEW RESIDENT BOARD & CARE OCCUPANCIES
PREFIX
MET
K241
Number of Exits – Story
Means of egress shall comply with the following:
1. The number of means of egress shall be in accordance with 7.4.
2. Not less than 2 separate exits shall be provided on every story.
3. Not less than 2 separate exits shall be accessible from every part of
every story.
Exit access, as required in number 3 above, shall be permitted to include a
single exit access path for the distances permitted as common paths of travel
by 32.3.2.5.2.
32.3.2.4.1, 32.3.2.4.2
K251
Dead-End Corridors and Common Paths of Travel
Dead-end corridors shall not exceed 30 feet.
Common paths of travel shall not exceed 75 feet.
32.3.2.5.2, 32.3.2.5.4
K261
Travel Distance to Exits
Travel distance from any point in a room to the nearest exit, measured in
accordance with Section 7.6, shall not exceed 250 feet.
32.3.2.6
Discharge from Exits
K271
Exit discharge shall comply with Section 7.7.
32.3.2.7
Illumination of Means of Egress
K281
Means of egress shall be illuminated in accordance with Section 7.8.
32.3.2.8
K291
Emergency Lighting
Emergency lighting in accordance with 7.9 shall be provided, unless each
sleeping room has a direct exit to the outside at the finished ground level.
32.3.2.9
K293
Exit Signage
Means of egress shall be marked in accordance with Section 7.10.
32.32.10
PROTECTION
K300
Protection – Other
List in the REMARKS section any LSC Section 32.2.3 Protection
requirements that are not addressed by the provided K-tags, but are deficient.
This information, along with the applicable Life Safety Code or NFPA
standard citation, should be included on Form CMS-2567.
Form CMS-2786W (10/2016)
Page 20