Form Cms-2786w - Fire Safety Survey Report - Icf-Iid (Large Facilities) 2012 Life Safety Code Page 15

ADVERTISEMENT

Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
NOT
ID
MET
N/A
REMARKS
PREFIX
(PROMPT OR SLOW EVACUATION)
MET
K371
Subdivision of Building Spaces – Smoke Compartments
Every sleeping room floor shall be divided into not less than two smoke
compartments of approximately the same size, unless one of the following
conditions exists:
1. Buildings having prompt or slow evacuation capability protected
throughout by an approved automatic sprinkler system installed in
accordance with 33.3.3.5.
2. Buildings having prompt or slow evacuation capability where each
sleeping room is provided with exterior ways of exit access arranged in
accordance with 7.5.3.
3. Buildings having prompt or slow evacuation capability where the
aggregate corridor length on each floor is not more than 150 feet.
33.3.3.7.1, 33.3.3.7.4 through 33.3.3.7.6
Subdivision of Building Spaces- Smoke Barrier Construction
K372
Required smoke barriers in accordance with 8.5.
Smoke partitions in accordance with Section 8.4 shall be permitted on stories
used for sleeping by not more than 30 residents. Smoke dampers shall not be
required. Additional smoke barriers shall be provided such that the travel
distance from a sleeping room corridor to a smoke barrier does not exceed
150 feet.
33.3.3.7.1, 33.3.3.7.2, 33.3.3.7.3, 33.3.3.7.8
K374
Subdivision of Building Spaces- Smoke Barrier Doors
Doors are in accordance with 8.5. Positive latching hardware shall not be
required on smoke barrier doors.
33.3.7.1, 33.3.3.7.7
K421
High-rise Buildings
All high-rise buildings shall be protected throughout by an approved,
supervised automatic sprinkler system in accordance with 33.3.3.5. Such
systems shall initiate the fire alarm system in accordance with 9.6.
33.3.3.5.3
IF THE LEVEL OF EVACUATION DIFFICULTY IS PROMPT OR SLOW,
STOP HERE & CONTINUE TO PART IV and PART V.
Form CMS-2786W (10/2016)