Form Cms-2786w - Fire Safety Survey Report - Icf-Iid (Large Facilities) 2012 Life Safety Code Page 14

ADVERTISEMENT

Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
NOT
ID
MET
N/A
REMARKS
PREFIX
(PROMPT OR SLOW EVACUATION)
MET
K363
Corridor – Doors
Doors shall have a fire protection rating of not less than 20 minutes, unless
the following condition exist:
1. Solid-bonded wood core doors of not less than 1-3/4 inches (4.4cm)
thickness shall be permitted to continue to be used.
2. In buildings protected throughout by an approved automatic sprinkler
system in accordance with 33.3.3.5, doors that are nonrated shall be
permitted to continue to be used.
3. Where automatic sprinkler protection is provided in the corridor in
accordance with 31.3.5.8, doors shall not be required to have a fire
protection rating but shall be in accordance with 8.4.3. The provisions of
8.4.3.5 shall not apply. Doors shall be equipped with latches for keeping
the doors tightly closed.
Walls and doors required by 33.3.3.6.1 and 33.3.3.6.2 shall be constructed as
smoke partitions in accordance with 8.4. The provisions of 8.4.3.5 shall not
apply.
Doors shall be self-closing or automatic-closing in accordance with 7.2.1.8.
Doors in walls separating sleeping rooms from corridors shall be automatic-
closing in accordance with 7.2.1.8.2 unless the following conditions exist:
1. Doors to sleeping rooms that have occupant- control locks such that
access is normally restricted to the occupants or staff personnel shall be
permitted to be self-closing.
2. In buildings protected throughout by an approved automatic sprinkler
system installed in accordance with 33.3.3.5, doors, other than doors to
hazardous areas, vertical openings, and exit enclosures, shall not be
required to be self-closing or automatic-closing.
33.3.3.6.4.1, 33.3.3.6.4.2, 33.3.3.6.4.3, 33.3.3.6.4.4, 33.3.3.6.5, 33.3.3.6.6.1,
33.3.6.6.2, 33.3.3.6.6.3
K364
Corridor - Openings
No louvers, transfer grills, operable transoms, or other air passages shall
penetrate such walls or doors, except properly installed heating and utility
installations.
33.3.3.6.5(3)
Form CMS-2786W (10/2016)
Page 14