Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
NOT
ID
MET
N/A
REMARKS
PREFIX
(PROMPT OR SLOW EVACUATION)
MET
K354
Sprinkler System - Out of Service
Where a required automatic sprinkler system is out of service for more than
10 hours in a 24-hour period, the authority having jurisdiction shall be notified,
and the building shall be evacuated or an approved fire watch system be
provided for all parties left unprotected by the shutdown until the sprinkler
system has been returned to service.
33.2.3.5.3, 9.7.6.1, 15.5.2 (NFPA 25)
Portable Fire Extinguishers
K355
Portable fire extinguishers shall be provided near hazardous areas in
accordance with 9.7.4.1.
33.3.3.5.7
K362
Corridors – Construction of Walls
Access shall be provided from every resident use area to not less than one
means of egress that is separated from all other rooms or spaces by walls
complying with 33.3.3.6.3 through 33.3.3.6.6.3 as modified by the following:
1. Rooms or spaces, other than sleeping rooms, protected throughout by an
approved automatic sprinkler system in accordance with 33.3.3.5.
2. Prompt evacuation capability facilities in buildings not over two stories in
height, where not less than one required means of egress from each
sleeping room provides a path of travel to the outside without traversing
any corridor or other spaces exposed to unprotected vertical openings,
living areas, and kitchens.
3. Rooms or spaces, other than sleeping rooms, provided with a smoke
detection and alarm system connected to activate the building evacuation
alarm. Furnishings, finishes, and furniture, in combination with all other
combustibles within the spaces, shall be of minimum quantity and
arranged so that a fully developed fire is unlikely to occur.
33.3.3.6.1, 33.3.3.6.1.1, 33.3.3.6.1.2, 33.3.3.6.1.3
Sleeping rooms shall be separated from corridors, living areas, and kitchens
by walls complying with 33.3.3.6.3 through 33.3.3.6.6.3.
Walls required shall have a fire resistance rating of not less than 1/2 hour
unless the following conditions apply:
1. In buildings protected throughout by an approved automatic sprinkler
system in accordance with 33.3.3.5, walls shall be smoke partitions in
accordance with 8.4. The provisions of 8.4.3.5 shall not apply.
2. In buildings not more than two stories in height that are classified as
prompt evacuation capability and that house not more than 30 residents,
walls shall be smoke partitions in accordance with 8.4. The provisions of
8.2.4.3.5 shall not apply.
33.3.3.6.2, 33.3.6.3.1, 33.3.6.3.2, 33.3.3.6.3.3
Form CMS-2786W (10/2016)